Nurse Call
CliniComm
Sentry E-Call
Sentry Wireless


 

 

Heritage MedCall Action Alert – March 16, 2005

Sentry Emergency Call System Smoke Detectors

Heritage MedCall received notice today that production of the Model HM-560 Smoke Detector has been discontinued.  Our supplier for over 10 years has cancelled production and will not fill our pending orders.

The good news is that we have been shipping our new HM-527 Host Panel (Rev. F) since late December which incorporates changes allowing the use of multiple source 4-wire smoke detectors currently available as our Part Number HM-560B.   

  • Please note the new HM-560B Smoke Detector is not compatible with any previous revision HM-527 Host Panel.
  • Smoke detector replacement for existing facilities will require replacement of all the smoke detectors and their Host Panel in any particular room.
  • If the room is equipped with a Wireless Pendant Receiver (HM-547) deriving power from the smoke detector wiring a Polarity Guard (HM-558) will need to be installed to protect the receiver during smoke detector operation.

The new HM-560B Smoke Detector includes the additional feature where the unit will report a Clean-Me trouble if the sensing chamber becomes too dirty for proper operation.

This only affects the Sentry Wired Emergency Call System and does not affect the new Sentry Wireless Emergency Call System.

If you have any questions concerning this ACTION ALERT, please do not hesitate to contact us.

HM-560B Tech Specs

 

 

 

Home       Copyright © 2004 Heritage MedCall, Inc     Site Map

 Print Page