PRODUCT DESCRIPTION

SMOKE DETECTOR

HM-560B

  • INTELLIGENT, SELF-DIAGNOSTIC

  • USER REPLACEABLE OPTICAL CHAMBER

  • LOW PROFILE DESIGN

  • PLUG-IN TERMINAL BLOCK

  • LED INDICATOR

  • MEETS NFPA 72

  • BUILT-IN 85 dB ELECTRONIC HORN

  • DUST COVER INCLUDED

HM-560B - Smoke Detector - Click for Larger Image


DESCRIPTION:

The Model HM-560 smoke detector is a low voltage, photoelectric unit designed for both single and multiple station use. The detector connects directly to the Sentry HM-527 Rev F host panel. Its sensor operates on the scattered light principle, and electronically compensates for ambient light conditions. The detector has its own 85dB temporal pattern horn and power-on LED.  Tamper resistant cover requires screwdriver to open hinged lid.

FEATURES:

Photoelectric sensor is designed to sample the air every 3 seconds and trigger an alarm if prescribed levels of smoke appear.  Self-diagnostics continually monitor its own sensitivity and operational status. Powered directly from the host panel, it will operate from system batteries when power goes out. Insect resistant screen minimizes nuisance alarms. Up to 4 additional detectors can be interconnected. The detectors alarm horn can be remotely activated by the host panel with the fire alarm interface option on the Master Console.

MOUNTING & WIRING:

The HM-560B smoke detector can mount to a standard single-gang electrical box, four-inch octagon or four-inch square electrical box, WIREMOLD No. 5739 fixture box.  The detector may also be flush mounted to walls or ceilings where local codes and or jurisdictions permit.  Wire using Sentry recommended West Penn wire WPW 253 4 pair wire and attach to included plug-in terminal block.

SPECIFICATIONS:

Minimum Voltage:  8.5 VDC
Maximum Voltage:  33 VDC
Typical Stand-by Current:  70
ma
Typical Alarm Current:  40 mA
Dimensions:  6.1” Diameter x 1.9” Deep

 

 

Sounder:  85dB at 10 feet
Wire size:  14 – 24 AWG
Heat Detector:  135
°F, 50 ft spacing
                          rate-of-rise 15
°F/min > 105°F
Weight:  8.8 oz

 

 

 

HM-560B Tech Specs pdf
HM-560B Install / Service Manual.PDF

 

 