Install Guide

 

PRODUCT DESCRIPTION

CARBON MONOXIDE DETECTOR 12V

HM-561

  • UL-2075 LISTED

  •  LOW CURRENT DRAW

  • END OF LIFE INDICATOR

  • 85 DB TEMPORAL-4 SOUNDER


DESCRIPTION:

UL 2075 listed Carbon Monoxide (CO) alarm approved for system use and meets testing requirements of UL 2034 listing.  End of Sensor life indicator warns when alarm replacement is needed.  Test / Silence button.  LED / Sounder - status indicator.

SPECIFICATIONS:

Operating Temp……………………………: 40° TO 100°F
Sounder………………………………………………...85db
Power………………………………………………...12VDC
Current
              Normal………………………………..8ma normal
              Alarm…………………………………75ma alarm
Relay Contact……………………………………….NO/NC
CO alarm level…………………..70 ppm/60-240 minutes

DIMENSIONS:

Width………………………………………….2.7” (6.9 cm)
Length…………………….…………………..6” (15.2 cm)
Depth…...…………………………..………….1.4” (3.6 cm)

 

INDICATORS:

LED

Sounder

Status

Green Off Safe Air
Red 4 rapid beeps every 5 seconds. Alarm
Flashing Amber every 30 – 60 sec. Chirp follows each LED flash. Trouble
Flashing Green every    1 – 2 Sec Chirps every 5 minutes. End of Life Sensor.

INSTALLATION:

Direct wall mountable using wall anchors.  18 – 22 gauge wire.

TESTING:

Press and hold Test / Hush button for CO test.  Sounder will beep 4 times, pause 5 seconds, beep 4 times and LED will turn green to indicate proper CO operation and relay will trip and reset after 9 seconds.

 

 

 