DESCRIPTION
The Model HM-585 End-Of-Line Resistor (EOL) is designed to provide supervision
on remote normally open contacts. All smoke detector and emergency call station
contact closures require one End-Of-Line.
The Model HM-585 End of Line device is wired to the wire connections on a single
smoke detector and on the last call station on a cable from the host panel. The
wires are 1.5" long to facilitate ease of installation and maintenance.
The presence of the End Of Line device is continuously monitored by the host
panel. A trouble signal will be received at the master console if this device,
or wiring to it is disconnected.
The Model HM-585 is covered with insulation tubing to eliminate electrical
shorts to other wiring or devices.
Note: The End Of Line Resistor will supervise the normally open contacts of
remote devices at the end of a cable. Multiple switches on a line must be
installed in a "daisy-chain" fashion with the EOL at the last switch
to provide proper supervision.
The Model HM-585 is a prewired 3300 ohm resistor with orange leads, stripped
& tinned.