|
   
WIRING DESIGN GUIDE
1.
SCOPE
This document is intended as
a guide to determine a wiring layout for Sentry installations. It is not a
substitute for good engineering practices. The installation design and
wiring specification must be specified by the project engineer. They will
be knowledgeable of the power requirements and any state and local codes.
2. BASIC RULES
A.
All power wiring from
terminal boards to host panels must be 18 gauge minimum.
B.
Never put more than 10
host panels (less with optional features) on a run from a terminal board. This
usually means a separate cable for each side of a hallway.
C.
Never bring a DC or data
cable back to a terminal board where it can form a loop. Loops attract noise and
transients and are NOT allowed.
D.
Always use 4 separate
wire colors for the power pair and data pair. The panels data line components
can be damaged if directly connected to the DC power leads. Sentry uses
white & black for DC + & -, and red & green for data + & - .
E.
The data pair MUST
always be accompanied by the DC common (-) wire, all the way back to the
console.
F.
Data wires must be
twisted pairs.
G.
Use shielded cable for
both data and audio when the intercom option is used.
H.
If you not sure about
something, call Sentry and ask.
3. VOLTAGE
REQUIREMENTS
All Sentry devices have been
specifically designed to minimize current requirements. All panels and other
Sentry devices
MUST have at least 9.0 volts
to perform properly.
4. VOLTAGE DROP
When designing the wiring of
a building for the installation of the Sentry system, current requirements and
voltage drops are major concerns. All wire and cable has resistance, and
this resistance will cause a voltage drop. Sentry devices require a minimum
voltage to operate, therefore voltage drops and line loses are an important
consideration. The amount of voltage drop is determined by the wire gauge, cable
length, and the current.
5.WIRE GAUGE
The larger the wire
conductor, the smaller the gauge number, and the greater current capacity.
Larger wire conductors will exhibit less voltage drop loss than small
conductors. Shorter cable lengths have less voltage drops than long cables.
Refer to section 15 for wire resistance.
6. RECOMMENDED
CABLE
Sentry recommends the use of
a 2 pair cable. One pair is 18 gauge wire size and the other pair is 22 gauge.
The 18 gauge pair is used for the DC voltage and the 22 gauge pair is used
for the serial data. Sentry recommends the West Penn Wire, 374 or
equivalent. Sentry documentation, wiring diagrams, and wire colors refer to this
West Penn cable.
7.CONFIGURATION
Sentry
systems are generally configured with each apartment operating independent of
one another. When a specific installation uses the Sentry Fire Alarm Interface,
the smoke detector horns can be activated by the console. This system feature
allows the apartment smoke detectors to act as auxiliary fire alarm announcement
devices. When the building or zone has a fire alarm, the interface will direct
the console to activate the smoke detect or horns in the apartments located
within that building or fire zone. This feature does not alter the fire alarm
system operation and is an optional, auxiliary sounding system only. The use of
the Sentry Fire Alarm Interface may be governed by local codes. Small apartments
are usually equipped with a Host Panel and a smoke detector. Larger apartments
can have up to 4 smoke detectors and up to 6 remote call stations.
8. CURRENT REQUIREMENTS
Device current requirements
are listed in Table 1. These currents are added to determine voltage drops.
"Standby" current is smoke detector current when it is not alarming.
|
HM-527 Host Panel
|
Maximum 0.045 Amps
|
45mA
|
|
HM-541Remote Call Switch
|
Maximum 0.012 Amps
|
12mA
|
|
HM-560 Smoke Detector
|
Standby 0.010 Amps
|
9mA
|
|
HM-560 Smoke Detector
|
Maximum 0.020 Amps
|
20mA
|
|
HM-547 Pendant Receiver
|
Standby 0.016 Amps
|
16mA
|
|
HM-681Dome Light
|
Typical 0.080 Amps
|
80mA
|
|
HM-523 Intercom Panel
|
Maximum 0.050 Amps
|
50mA
|
|
HM-694 Security Keypad
|
Maximum 0.045 Amps
|
45mA
|
|
HM-685 Strobe Light
|
Typical 0.425 Amps
|
425mA
|
DEVICE CURRENT REQUIREMENTS
TABLE 1
|
|
STANDBY
|
ALARM
|
|
1 Host Panel and 1 Smoke Detector
|
55mA
|
115mA
|
|
1 Host Panel and 2 Smoke Detectors
|
65mA
|
185mA
|
|
1 Host Panel and 3 Smoke Detectors
|
75mA
|
255mA
|
|
1 Host Panel and 4 Smoke Detectors
|
85mA
|
325mA
|
APARTMENT CURRENT REQUIREMENTS
TABLE 2
9. OPTIONAL APARTMENT
DEVICES
Apartments can include
optional equipment powered through the panel wiring. Some of these devices
include: Wireless pendant receivers, dome lights, intercom panels, and remote
call switches. Some installations include program options which allow control of
smoke horns, dome lights, and intercom as PA speakers. It is important to
understand which interfaces are ordered with a system to properly determine
total current draw.
Typical installations,
(without fire interface): each apartment draws the current listed under STANDBY
in Table 2 above. When smoke is detected the current draw increases to the
amount shown under ALARM. For this type of installation, worst case estimate of
current draw is figured with all apartments on a common power and data cable to
be in STANDBY, except the furthest apartment is in ALARM. The worst case voltage
drop is calculated from this current.
Fire Alarm Interface:
all the smoke detectors in the apartments connected to the same cable can go
into ALARM at the same time, therefore every apartment on a common power and
data cable will be drawing the maximum current. The worst case voltage drop is
calculated from this current total.
The number of apartments
that can be connected to a common power and data cable is significantly lower
when the system is connected to a fire alarm interface. This is because of the
higher voltage drops associated with the higher current from all the smoke
detectors alarming at one time.
Seldom will more than 1 of 2
dome lights be lit at once, but when a fire alarm interface is used to activate
smoke horns, and turn on the dome light during a smoke alarm, ALL dome lights
will turn on at once, along with the smoke horns, an additional load of 160mA
per apartment. The P.A. All-Call feature will activate all P.A. amplifiers in
the intercoms simultaneously.
10. CABLE LIMITATIONS
Table 3 lists the maximum
recommended number of apartments on the same power and data cable in a typical
installation. For the calculations, a power supply of 13.0 Volts and the minimum
voltage requirement of 9.0 Volts at the host panel is used. This table does not
calculate any of the possible option. Table 4 lists the same equipment and
options but is figured using a fire alarm interface.
|
Cable between panels
|
1 Smoke Detector
|
2 Detectors
|
3 Detectors
|
4 Detectors
|
|
40
|
16
|
15
|
14
|
13
|
|
50
|
14
|
13
|
12
|
11
|
|
60
|
13
|
12
|
10
|
9
|
|
70
|
12
|
10
|
9
|
8
|
|
80
|
11
|
10
|
9
|
8
|
|
90
|
10
|
9
|
8
|
7
|
|
100
|
9
|
8
|
7
|
6
|
|
110
|
9
|
8
|
7
|
6
|
|
120
|
8
|
7
|
6
|
5
|
|
150
|
7
|
6
|
5
|
5
|
|
200
|
6
|
5
|
4
|
3
|
Notes: Last apartment of the cable in full alarm. Other
apartments in standby mode. 18
Gauge power cable pair. Cable run
to supply figured at same length as between panels.
RECOMMENDED MAXIMUM NUMBER OF APARTMENTS ON CABLE
Table 3
|
Cable between panels
|
1 Smoke Detector
|
2 Detectors
|
3 Detectors
|
4 Detectors
|
|
40
|
11
|
8
|
7
|
6
|
|
50
|
9
|
7
|
6
|
5
|
|
60
|
9
|
7
|
5
|
5
|
|
70
|
8
|
6
|
5
|
4
|
|
80
|
7
|
6
|
5
|
4
|
|
90
|
7
|
5
|
4
|
4
|
|
100
|
6
|
5
|
4
|
3
|
|
110
|
6
|
5
|
4
|
3
|
|
120
|
6
|
4
|
4
|
3
|
|
150
|
5
|
4
|
3
|
3
|
|
200
|
4
|
3
|
3
|
2
|
Notes: All apartments on the cable in full alarm. 18 Gauge
power cable pair. Cable run to supply figured at same length as between panels.
RECOMMENDED MAXIMUM NUMBER OF APARTMENTS ON CABLE
Table 4
11. GROUPING
In an effort to minimize
voltage drop, wire apartments in groups of no greater than the number listed in
tables 3 & 4. Figure 1 on page 6 shows wiring layout examples, the incorrect
methods violate the number of apartments rule.
In high-rise buildings, it
proves wise to install all power supplies on the same floor, about center to the
building. 10 or 12 gauge wire supplies the terminal board locations. This
configuration make servicing easier and protects the system from lightning
damage. See the example on page 7.
12. SPECIAL CABLING
Some system designs require
longer distances between the apartment groupings and the power supply. In these
cases, larger wire conductors are needed to reduce voltage drop. Usually a 14,
12, or 10 gauge wire pair is used for DC voltage, with a separate 22 gauge data
pair.
In most cases the heavy duty
wire is only required between the power supply and the first apartment, then the
apartments are usually arranged in groups that can use the recommended 2 pair
cable. Use this guide to determine current, then chose an appropriate wire to
keep the apartment panel voltage above 9 volts.
13. DATA WIRE PAIR
The data wire pair is
specified by Sentry as 22 gauge. This gauge is adequate for data on most
installations of up to a half mile. If the data cable will be run between an
apartment group and console, underground, or greater than 1000 feet, it is
recommended to install an 18 gauge.
A common conductor
MUST run with all data pairs. Where a cable is required for data only, the cable
must include a shield or drain wire.
14. AUDIO CABLES
Installations involving
audio communications use a separate shielded audio cable that runs along side
the power/data pair. See the audio wiring diagrams for the recommended cable.
Long data lines running parallel to audio should also be shielded.
Always ground the shield (or
drain wire) ONLY at the console end by connecting to the computers case.
15. WIRE RESISTANCE
Table 5 shows the DC
resistance of copper wire at the gauge sizes mentioned in this guide.
|
Wire Gauge
|
Ohms per 1000 feet
|
|
22
|
16.140
|
|
18
|
6.385
|
|
14
|
2.525
|
|
12
|
1.588
|
|
10
|
0.998
|
Wire Resistance (copper)
Table 5
Back to top
|